← → arrow keys · swipe · buttons below
A synchronous machine does not present a fixed impedance during a fault. Three time-frame reactances apply, corresponding to the decay of flux in successive winding layers:
When a fault occurs at an instant other than the voltage peak, the physical constraint that current cannot change instantaneously forces a DC offset onto the AC fault current waveform.
AC waveform showing a fault current that starts at zero and decays from a high asymmetrical peak. Three envelopes labeled: I'' (sub-transient, red), I' (transient, yellow), I (steady state, grey). A decaying DC offset dashed line is shown below the waveform. Time axis with markers at 50ms, 200ms, 1s. Dark background, engineering style.
For fault studies, the transformer is modelled as a series leakage impedance (resistance + reactance). The magnetising branch is neglected because it is typically 2000% of rated impedance versus 10% for the leakage.
Zero-sequence current requires an earth return path. The transformer winding configuration determines whether zero-sequence current can flow on each side.
Line impedances are calculated using Carson's equations, which account for conductor geometry and the earth return path. The positive-sequence impedance depends on conductor self-impedance and mutual coupling between phase conductors.
During a phase-to-earth fault, the fault loop impedance includes the line positive-sequence path to the fault plus the earth return path from fault back to source. A distance relay calibrated only for will over-read (under-reach) unless the earth path contribution is subtracted.
Given: 132 kV single-circuit overhead line, 100 km. . .